AEP transducers / TPL2C / Pressure transducer

Pressure transducers belonging to TPL2C series have been designed to be used as immersion level measuring instruments, employable in manifold fields dealing with controlling, regulating and monitoring activities.
Installation of the sensors requires their total immersion at maximum depth, where measurements to determine levels non-dense substances are performed from.
The sensitive part in contact with pressure, is entirely made of AISI 316L stainless steel resistant to corrosion.
Protection class IP68 (permanent immersion)
Process coupling 1/4″ GAS Female
POLYURETHANE cable outlet with length on request
Power supply 12 to 24 Vdc

Category:

설명

Pressure transmitters to permanent IMMERSION for level measures Nominal RELATIVE pressures from 300mbar (3mH2O) to 20bar (200mH2O) AMPLIFIED output 4-20mA 2 wires Linearity and Hysteresis 0,10%

Pressure transducers belonging to TPL2C series have been designed to be used as immersion level measuring instruments, employable in manifold fields dealing with controlling, regulating and monitoring activities.
Installation of the sensors requires their total immersion (IP68 protection class) at maximum depth, where measurements to determine levels non-dense substances are performed from.
The sensitive part in contact with pressure, and the whole body as well, is entirely made of AISI 316L corrosion-proof stainless steel.
Electronic section, realised via SMD technology, consists of a high precision instrumental amplifier and a stable supplier, protected against short circuits and polarity inversion.
Every pressure transmitter is entirely LASER welded and completely resin-encapsulated, to ensure insensitivity and a high degree of hermetic tight.
During production cycle, pressure transmitters are thermally compensated, tested and individually calibrated with the use of completely automated stations that analyse and record data.

Dimensions[mm]

Technical Data

 
RELATIVE PRESSURE (R)
Zero at atmospheric pressure
bar 0.1 0.2 0.3 0.4 0.5 1
mH2O 1 2 3 4 5 10
bar 2 3,5 5 7.5 10 15
mH2O 20 35 50 75 100 150
LINEARITY and HYSTERESIS ± 0.10 %
TEMPERATURE EFFECT (1°C)
a) on zero
b) on sensitivity
≤ ± 0.015%
≤ ± 0.015%
NOMINAL SENSITIVITY CALIBRATION TOLERANCE 4-20mA (2 wires)
≤ ± 0.1%
NOMINAL POWER SUPPLY 11.5 – 24Vdc
MAX. POWER SUPPLY
MAX. ABSORPTION:
LOADING RESISTANCE:
INSULATION RESISTANCE
ZERO BALANCE
RESPONSE FREQUENCY
28Vdc
20mA
from 0 to 470Ω
>2 GΩ
£ ± 1%
0.5 KHz
LIMIT MECHANICAL VALUES REFERRED TO NOMINAL PRESSURE:
a) service pressure
b) max. permissible pressure
c) breaking pressure
d) highly dynamic pressure
 
100%
150%
>300%
75%
REFERENCE TEMPERATURE
WORKING TEMPERATURE RANGE
STORAGE TEMPERATURE RANGE
+23°C
-10/+50°C
-20/+70°C
PROTECTION CLASS (EN 60529)
SENSOR
and BODY EXECUTION MATERIAL
PROTECTIVE CAP MATERIAL

ELECTRICAL CONNECTION
IP68 (100h at 100m water column)
AISI 316L
POM Resina acetalica/ Acetal
Cavo / Cable

OPTIONS

POLYURETHANE CABLE Al metro / Per meter

Electrical connections

(1) Be sure that while wiring compensating pipe remains open.
Connected to body of the pressure transmitter

상품평

아직 상품평이 없습니다.

“AEP transducers / TPL2C / Pressure transducer”의 첫 상품평을 남겨주세요